This system used Japanese type P class 1 as the design blueprint. Also up-to date electronic materials are generally used that the error is minimized, working acuracy enhanced and trouble rate greatly lowered.
Features
- Face board function:
- Computer-class board design (multi-color) is used for much clear characters without fading, easier maintenece, better functioning and display, and easy to use.
- Circuit characteristics:
- Imported relay circuits are used for power saving when superising and greater output to minimized trouble and obtaining longer life.
- Thundering rod is attached to the circuit to avoid high tension breaking through that the line voltage is regulated to ensure accurate actioni. The end resistance is installed on the line board.
- An independent switch is given to each circuit and it is turned to "OFF" position when in use. The breaking error is eliminated. The outside line end is attaced to the line board directly.
- Outside line short circuit lamp is available to each 5L connecting point to identify short circuit or sensing action.
- Potential line:
- the CPU line may recover the first firesignal automaticcally and let the second signal scaning detecting to make sure any fire alarm positively.
- Source basic board:
- The controlling outside line indicating lamp and area bell are controlled by relay for stable output. Breaking indicator lamp is attached along the fuse points for easy maintenece and inspection.
- Thundering rods are attached to outside lines for safety purpose. Stable IC control is used for charging lines to ensure good charging and longer battery life.
- Configuration:
- Outside lines are guided into grooves to connect inside lines so to avoid short circuit. Computer connecting ends are used for inside lines that replacements may be made by remove the joint only in case of trouble to simplify the process and speed the maintenence.
- A special design is on the break of the face board for monitoring the general operation of the machine. The flash of LED indicates normal working of IC supervising function.
- Type: CL9600 Typc P First Class
- Standard: CNS 8877 Z2044
- Regular source AC110V or AC220V (50/60Hz)
- Reserve Source: DC24V close type, maintenance-free lead acid battery
- Circuit voltage: Regular DC24V, Allowance DC19V-DC30V
- End resistance: 10K ohm 1/4-1/W installed on the extreme end of the detector
- Exterior resistance: Below 50 ohms after circuit action (When exterior line short circuit)
- Detector: Smoke detecting type, differential type, constant temperature type
- Main unit buzzing: Built-in buzzer DC24V 90dB (on and off type)
- Consolidated plate indicating lamp: Within 30V30W maimum connections (fire circuit number x 1.3)pieces
- Consolidated plate rings: Within 24V 100mA maximum connections (circuit number x 1.3) pieces
- Consolidated plate pressing lock: To be used with area circuits or an independent circuit
- Water alarm; Point and line connecting by pump starter (No voltage A point connecting)
- Point connecting: (No voltage A point connecting) AC220V 5A(550VA)
- Telephone set: Two telephone receivers to each switchborad
- Appearence: Steel plate 1.6 M/M color lvory (baking finish)
- Spares: End resistance, fuses and line chart as required number of circuits
Main Products