3/1 Phase Micro - Controlled On - Line PWM UPS
Product ID: UP
- Input
- Voltage: see table
- Voltage: range: +10%-15%
- Frequency: 47/63Hz
- Power walk-in: 55
- Protection: circuit breaker, RFI filter
- Power factor: 0.8
- Output:
- Voltage: see table, no DC component
- Regulation: +/-1%
- Freq. tracking range: +/-1, +2Hz, selectable
- Slew rate: 1Hz/Sec.
- Overload: 125% 10 min., 150% 30 sec, 1000% 1 cycle
- Load P.F.: 0.7
- Waveform: sinusoidal
- T.H.D: less than 2% (at linear load)
- Crest factor: 3:1
- Protection: overload and short circuit
- Dynamic response on 100% load change: +/-2%
- Transition time: UPS to and from line, less than 0.5msec
- Rejection ratio: more than 100dB
- Environment:
- Ambient temperature, operating: -10 to 40 Celsius; storage: -20 to 60 Celsius
- Relative humidity: 95%max., non condensation
- Altitude: 1500m w/o derating
- EMI suppression: according to EN55022-B
- UPS standard: IEC 146-4
- MTBF: 100,000 hrs., 250,000 hrs. with static switch
- Power solutions for all your needs
- All specifications given are typical and subject to change without notice.
- L.C.D. data:
- Input: voltage
- Output: current & voltage
- Bypass & inverter: voltage, current & frequency
- Battery: voltage
- Temperature: heat-sink
- Real time and accumulated operational time log (events memory)
- Options:
- Maintenance bypass
- Extended battery backup
- Any other voltage or frequency
- Communication options:
- RS232: modem, computer
- Alarm: shutdown systems
- Remote indication panel
| Model | 6K | 8K | 10K | 15K | 20K |
|---|---|---|---|---|---|
| Input / voltage (V) | 3 x 400 | 3 x 400 | 3 x 400 | 3 x 400 | 3 x 400 |
| Input / current (A) batteries in charged condition | 3 x 8.5 | 3 x 13 | 3 x 15 | 3 x 26 | 3 x 30 |
| Input / required ext. input MCB (A) | 3 x 16 | 3 x 20 | 3 x 25 | 3 x 40 | 3 x 50 |
| Output / voltage (V) | 230 | 230 | 230 | 230 | 230 |
| Output / power (KVA) | 6 | 8 | 10 | 15 | 20 |
| Output / power (KW) | 4.2 | 5.6 | 7 | 10.5 | 14 |
| Output / current (A) | 26 | 35 | 43.5 | 65 | 87 |
| Output / Efficiency AC-AC @100% load (%) | 89.5 | 90 | 90 | 90 | 90 |
| Output / Efficiency AC-AC @50% load (%) | 88.5 | 89 | 89 | 89 | 89 |
| Output / full load, heat dissipation (W), 1W=3.4 BTU | 493 | 622 | 778 | 1167 | 1556 |
| Output / inverter efficiency, at 100% load (%) | 95 | 93.5 | 93.5 | 93.5 | 94 |
| Backup operation / backup (min) 100% load | 15 | 9 | 6 | 10 | 6 |
| Backup operation / backup (min) 50% load | 40 | 24 | 17 | 28 | 19 |
| Backup operation / battery recharge time | Approx. 10 hours | Approx. 10 hours | Approx. 10 hours | Approx. 10 hours | Approx. 10 hours |
| Backup operation / batteries (12VDC each) | Internal 32 x 7 AH | Internal 32 x 7 AH | Internal 32 x 7 AH | Internal 32 x 15 AH | Internal 32 x 15 AH |
| Backup operation / expected battery life | 5 years | 5 years | 5 years | 5 years | 5 years |
| Physical / size (cm) H | 63 | 63 | 63 | 73 | 73 |
| Physical / size (cm) W | 24 | 24 | 24 | 24 | 24 |
| Physical / size (cm) D | 65 | 65 | 65 | 80 | 80 |
| Physical / weight (kg), W/O batteries | 95 | 110 | 120 | 140 | 150 |
| Physical / audible noise (dB), at 1.5m distance | 51 | 52 | 52 | 53 | 56 |
Main Products:
compact UPS, new release, power system