HPD Series

Product ID: HPD 15-20

Send Inquiry
The XT Series has been available since 1983. It continues to be one of our top selling products lines, achieving the highest volume sales in 1995. It was the launch into the emerging phase of power supplies which were a significant improvement in design and specifications from existing power supplies. The goal of the Xantrex engineering team was to maximize the use of common components, reduce building and testing times and reduce costs. New features include flexible interfacing with any future optional control card, digital display meters, and molded plastic panels which reduced overall material costs. The XT line has been used by our customers in virtually every part of their manufacturing process - from design to production test. The XT can be combined with HPD units for higher power requirements. It can be controlled by using analog programming or by optional interface cards such as the RS232, GPIB, SAMI. The HPD Series answered market demands for a higher powered, lightweight unit. This was achieved by using switch mode technology, including a linear post regular and reducing the size of components. It offer 300 watts of power packed into a 1/4 width rack, weighing only 8 pounds. Modularity and ease of manufacture were also key issues on the design. The XT and HPD Series use the same front panel control board, internal interface boards, and mechanical housing. They are available in single, triple, and quad configurations. Both series are rack mountable.
options.
Models (V-A) HPD 15-20 HPD 30-10 HPD 60-5
Output Ratings: N/A N/A N/A
Output Voltage 0-15V 0-30V 0-60V
Output Current 0-20A 0-10A 0-5A
Output Power 300W 300W 300W
Line Regulation: N/A N/A N/A
Voltage (0.01% of V max. + 2mV) 3.5mV 5mV 8mV
Current (0.01% of I max. + 1mA) 3mA 2mA 1.5mA
Load Regulation: N/A N/A N/A
Voltage (0.01% of V max. + 2mV) 3.5mV 5mV 8mV
Current (0.01% of I max. + 1mA) 3mA 5mA 1.5mA
Meter Accuracy: N/A N/A N/A
Voltage (1% of V max. + 1 count) 0.25V 0.4V 0.7V
Current (1% of I max. + 1 count) 0.3A 0.2A 0.06A
Output Noise and Ripple at rear output (20Hz - 20MHz) 5mVrms / 100mVp-p 5mVrms / 100mVp-p 5mVrms / 100mVp-p
Stability: N/A N/A N/A
Voltage (0.02% of V max.) 3mV 6mV 12mV
Current (0.03% of I max.) 6mA 3mA 1.5mA
Temperature Coefficient N/A N/A N/A
Voltage (0.015% of V max./Celsius) 2.25mV 4.5mV 9mV
Current (0.02% of I max./Celsius) 4mA 2mA 1mA
Front Panel Voltage Control Resolution (0.02% of V max.) 3mV 6mV 12mV
Program Resolution: N/A N/A N/A
Voltage 2.4mV 4.7mV 9.3mV
Current 2.8mV 1.4mV 0.7mV
OVP 2.4mV 4.7mV 9.3mV
Program Accuracy: N/A N/A N/A
Voltage 60mV 70mV 90mV
N/A ±0.1% ±0.1% ±0.12%
Current 75mV 50mV 25mV
N/A ±0.12% ±0.12% ±0.1%
OVP 150V 300mV 600mV
Readback Resolution: N/A N/A N/A
Voltage 2.4mV 4.7mV 9.3mV
Current 2.8mA 1.4mA 0.7mA
Readback Accuracy: N/A N/A N/A
Voltage 45mV 90mV 175mV
N/A ±0.3% ±0.3% ±0.3%
Current 75mA 40mA 25mA
±0.12% ±0.12% ±0.1%
Specifications
  • Specification are warranted over a temperature range of 0 - 30 Celsius with default local sensing. Above 30 Celsius, derate output linearly to zero at 70 Celsius.
  • For input voltage variation over the AC input voltage range, with constant rated load.
  • For 0 - 100% load variation, with constant nominal line voltage.
  • Drift over 8 hours after 60-minute warmup.
  • Change in output per Celsius change in ambient temperature, with constant line and load.
  • AC Input (default)
    • Single Unit: 104 - 127 Vac at 6Arms
    • Dual Unit: 104 - 127 Vac at 12Arms
  • Maximum Voltage Differential From Output To Safety Ground
    • 400Vdc.
  • Operating Ambient Temperature
    • 0 - 30 Celsius with default local sensing.
    • Above 30 Celsius, derate output linearly to zero at 70 Celsius.
  • Storage Temperature Rang
    • -55 Celsius to +85 Celsius.
  • Humidity Range
    • 0 - 80% RH non-condensing.
  • Voltage Mode Transient Response Time
    • < 500mus recovery to 50mV band for±50% load change in the range of 25% to 100% of the rated load.
  • Switching Frequency
    • 100kHz (nominal)
  • Front Panel Control
    • 10-turn voltage and 1-turn current potentiometers (10-turn current control optional).
  • Front Panel Voltage Control Resolution
    • 0.02% of V max.
  • Weight: 3.5kg (7.7 lb)
  • Agency Approvals
    • CSA, FCC part 15, subpart J, class.
    • A standards for radiated and conducted emissions.
    • CE.
  • Standard AC Input
    • Standard 115Vac.
  • Accessories And Options
    • M2-220Vac 47 - 63 Hz input.
    • M2s-switch selectable i/p voltage from 115Vac to 220Vac.
  • Mixed HPD/XT units
  • M11: 10-turn current potentiometer
  • M13: locking bushings
  • Programming Options
    • APG-internal analog programming.
    • Includes OVP, remote on/off switch, master/slave tracking.
    • GPIB.
    • RS232.
    • SAMI - (single address multichannel interface).
    • For more information on these interfaces, see pages 36 - 42.
Features
  • Over voltage protection
  • Internal digital interfaces.
  • 10 turn potentiometer
  • Multiple configurations
  • Remote sense
  • Analog bar graph
  • Short circuit proof output
  • Small size
  • Available in dual quad configurations
  • Rack mountable
  • Current limit

Main Products